HOW OUR ICE BUILDER WORKS
Refrigerant runs through a coil matrix inside an insulated water tank, building a bank of ice around the coils during off-peak or non-operating hours. During the next cycle of plant operations, the stored 32°F ice water is delivered from the tank to heat exchangers, kettle jackets, and other process equipment for various plant cooling loads and is then returned to the unit to repeat the process.
A low-pressure blower bubbles air up through a single perforated stainless steel pipe at the bottom of the tank. That air agitation melts the ice bank evenly and keeps outgoing water at a constant low temperature for as long as ice remains on the coils.
FEATURES & BENEFITS
- Lower equipment investment – Using our Ice Builder allows you to size refrigeration equipment for average demand rather than peak demand.
- Lower operating costs – Build ice when local electric rates are lowest, and run your refrigeration efficiently at all times.
- Constant cold water – Air agitation keeps outgoing water at a steady low temperature as long as ice is on the coils.
- Fully automatic – Automatic ice thickness and water level controls balance refrigeration supply to demand.
- Easy to maintain – The capped air distribution pipe blows clear of sediment by removing a single cap.
- Indoor or outdoor – Units come fully equipped for indoor or outdoor installation, and can be custom built to fit your available space.
SPECIFICATIONS
- Capacity: 1,000 to 142,000 lbs. of ice; multiple dimensions available for the same capacity
- Rating: 1,000 lbs. of ice per ton of refrigeration, based on 2½” ice thickness
- Refrigerant: ammonia (flooded or direct expansion), Freon, or glycol
- Construction: insulated heavy steel plate tank with interlocking insulated covers
- Coils: heavy-wall Schedule 40 steel pipe
- Air agitation: 1½” stainless steel distributor with low-pressure blower
- Controls: automatic ice thickness control and automatic water level control